AllBestEssays.com - All Best Essays, Term Papers and Book Report
Search

Felicity Paper

Essay by   •  December 7, 2013  •  Case Study  •  1,626 Words (7 Pages)  •  1,325 Views

Essay Preview: Felicity Paper

Report this essay
Page 1 of 7

D:1208DocumentsAddendum No 2.docx

GREEN VALLEY MEDICAL CENTER

ADDENDUM

NO:

2

PROJECT:

DATE:

TO:

GENERAL:

ITEM 1:

Green Valley Medical Center

New Hospital

April 25, 2013

ALL CONTRACT BIDDERS OF RECORD, OWNER,

CONSULTING ENGINEERS, PLAN SERVICES AND OTHER

ORGANIZATIONS CONCERNED WITH THIS PROJECT.

The following changes, additions or deletions are for the above

referenced contract documents; all other conditions shall remain the

same. This addendum forms a part of the contract documents and

modifies them as follows:

General Bid Information Items:

1. Request for Proposal:

a. Article 3 Introduction and General Instructions:

i. Paragraph 1.a: Delete the words "Hard Bid". The

submitted cost / price shall be a "Guaranteed Maximum

Price Proposal" with a list of exceptions. The pricing

shall include the level of specified materials and

products listed in the addenda. Alternative products will

only be reviewed through the Value Engineering

Suggestions. An updated schedule of values is attached

to this addendum and now includes a line for a "Project

Contingency". This form shall be used to submit your

price.

ii. Per Paragraph 1.d, the contractor may submit a

separate list of value engineering suggestions at the

time of the submittal.

b. Article 9 Owner Responsibility - Clarifications:

i. Data Communications, Structured Cabling - installation

shall be the contractor's responsibility.

ii. Access Control, Intrusion, Electronic Surveillance -

cabling and device installation shall be the contractor's

responsibility.

iii. Fire Alarm - wiring and device installation shall be the

contractor's responsibility.

iv. Restaurant and Laundry Equipment - Purchased by

Owner. Contractor to coordinate installation with

building utilities.

v. Hospital Equipment - Purchased by Owner. Contractor

D:1208DocumentsAddendum No 2.docx

ITEM 2:

to coordinate installation with building utilities.

vi. Window Coverings - Furnished and installed by the

contractor.

vii. Furnishings by Owner.

Interiors Package (dated 02.14.13):

1. Wall Types:

a. Refer to code analysis sheets in Core/Shell Package for fire

rated partitions and smoke partitions, sheets g1.2 through

g1.4. All corridor walls, fire and smoke walls, walls between

departments, office walls, conference room walls extend to

concrete deck above.

b. 2nd floor - all patient room and corridor partitions extend to

concrete deck.

c. All gypsum board partitions and ceilings shall have a Level 5

finish.

2. Paint:

a. Dunn Edwards Healthcare Specification - see attached.

b. Provide (1) accent wall per room.

c. Lobbies and Restaurant will have multiple accent colors.

3. Wall Protection / Cubicle Curtains: Basis of Design InPro

Corporation, as shown on wall protection plans, sheets B-a5.0,

B-a5.1, 1-a5.0, 1-a5.1, 1-a5.2, 1-a5.3, 2-a5.0, 2-a5.1

a. PVC Wall Protection - Rigid Wall Sheet IPC #405 Velvet

Texture

b. Bumper Guards - IPC #1500

c. Handrail - IPC #3500VV

d. Corner Guards - IPC #150

e. Wall Ends / Guards - IPC #160D

f. Cubicle Curtain Track - InPro Whisper Cube Track with

IPC#CE9038 ball and chain carrier, curtains by owner.

4. OR Walls: Basis of Design Altro Whiterock hygienic wall system

a. Provide at all walls in OR Rooms, Sterile Core, and Cath

Lab.

b. Hot-welded joints

c. Must be installed by a professional installer, preferably one

that has attended an Altro Whiterock installation clinic.

5. Interior Doors:

a. Solid core Acrovyn doors with stainless steel edges. Wood

doors - 5 ply by Algoma or equal. Factory finished and

hardware prepared.

b. Refer to updated door schedules on revised sheets B-a4.0,

1-a4.2, 1-a4.3, 2-a4.1 for door types.

6.

...

...

Download as:   txt (12 Kb)   pdf (146.1 Kb)   docx (16.5 Kb)  
Continue for 6 more pages »
Only available on AllBestEssays.com